DRAINING AND FLUSHING
Burn harzard.
Hot water discharge.
Keep hands clear of drain
valve discharge.
It is recommended that the water heater storage tank be drained
and ushed every 6 months to reduce sediment buildup. The
water heater should be drained if being shut down during freezing
temperatures.
To Drain the Water Heater Storage Tank:
1. Turn off the electrical supply to the water heater.
2. Turn off the gas supply at the Main Gas Shutoff Valve if
the water heater is going to be shut down for an extended
period.
3. Ensure the cold water inlet valve is open.
4. Open a nearby hot water faucet and let the water run until
the water is no longer hot.
5. Close the cold water inlet valve to the water heater.
6. Connect a hose to the water heater drain valve and terminate
it to an adequate drain.
7. Open the water heater drain valve and allow all the water to
drain from the storage tank.
8. Close the water heater drain valve when all water in the
storage tank has drained.
9. Close the hot water faucet opened in Step 4.
10. If the water heater is going to be shut down for an extended
period, the drain valve should be left open.
To Flush the Water Heater Storage Tank:
1. Turn off the electrical supply to the water heater.
2. Ensure the cold water inlet valve is open.
3. Open a nearby hot water faucet and let the water run until
the water is no longer hot. Then close the hot water faucet.
4. Connect a hose to the drain valve and terminate it to an
adequate drain.
5. Ensure the drain hose is secured before and during the
entire ushing procedure. Flushing is performed with system
water pressure applied to the water heater.
6. Open the water heater drain valve to ush the storage tank.
7. Flush the water heater storage tank to remove sediment and
allow the water to ow until it runs clean.
8. Close the water heater drain valve when ushing is completed.
9. Remove the drain hose.
10. Fill the water heater - see Filling The Water Heater in this manual.
11. Turn on the electrical supply to place the water heater back
in operation.
12. Turn on the gas supply to the water heater at the Main Gas
Shutoff Valve.
13. Allow the water heater to complete several heating cycles to
ensure it is operating properly.
PERIODIC REMOVAL OF LIME DEPOSITS FROM
TANK TYPE COMMERCIAL WATER HEATERS
The amount of calcium carbonate (lime) released from water is
in direct proportion to water temperature and usage, see chart.
The higher the water temperature or water usage, the more lime
deposits are dropped out of the water. This is the lime scale
which forms in pipes, heaters and on cooking utensils.
Lime accumulation may affect the life of equipment, the efciency
of the heater, and fuel consumption characteristics. The usage of
water softening equipment greatly reduces the hardness of the
water. However, this equipment does not always remove all of
the hardness (lime). For this reason it is recommended that a
regular schedule for deliming be maintained.
The time between cleaning will vary from weeks to years
depending upon water conditions and usage.
The depth of lime buildup should be measured periodically.
Heaters equipped with cleanouts will have about 2" of lime
buildup when the level of lime has reached the bottom of the
cleanout opening. A schedule for deliming should then be set up
based on the amount of time it would take for a 1" buildup of lime.
It is recommended that the water heater initially be inspected
after 6 months.
Example 1:
Initial inspection after 6 months shows 1/2" of lime accumulation.
Therefore, the heater should be delimed once a year.
Example 2:
Initial inspection after 6 months shows 2" of lime accumulation.
Therefore, the heater should be delimed every 3 months.
FIGURE 26.
DELIMING SOLVENTS
UN•LIME is recommended for deliming. UN•LIME is a patented
food grade acid which is safe to handle and does not create the
harmful fumes which are associated with other products.
UN•LIME may be obtained from your dealer, distributor or water
heater manufacturer. Order Part Number 9005416105, 1 gallon,
packed 4 gallons per case or Part Number 9005417105, 5 gallon
container.